Menu
Back
  1. Products
  2. Automation technology - Voltage and Power Supply
  3. M12-K
  4. M12 Female cable connector, Contacts: 4+PE, 8.0-13.0 mm, unshielded, screw clamp, IP67, UL 2237 in preparation, with PE connection
Part no.: 99 0700 37 05

M12 Female cable connector, Contacts: 4+PE, 8.0-13.0 mm, unshielded, screw clamp, IP67, UL 2237 in preparation, with PE connection

M12-K, series 824, Automation Technology - Voltage and Power Supply
Compare product
Downloads
This female cable connector with screw locking and a pin count of 4+PE is according to its protection class IP67 Dust-tight and has complete protection against contact and protection against temporary immersion. It can be used in areas with a pollution degree of 3. In places where contamination can occur that is conductive or can become conductive through condensation. With temperatures ranges of -40 °C/85 °C is this unshielded M12-K coded female cable connector designed for both severe cold and severe heat. Due to the qualified rated voltage of 630 V and the rated current of 12,0 A it is perfectly tuned for its field of application. It complies with the type standard DIN EN IEC 61076-2-111:2018-10 and VDE 0687-76-2-111:2018-10.
General features
Moreless
Part no. 99 0700 37 05
Connector design Female cable connector
Type standard DIN EN IEC 61076-2-111:2018-10;VDE 0687-76-2-111:2018-10
Version Connector pin straight
Connector locking system screw
Termination screw clamp
Degree of protection IP67
Cross-sectional area max. 1.50 mm² with ferrule / max. 2.50 mm² without ferrule / AWG 16 with wire-end ferrule / AWG 14 without wire-end ferrule
Cable outlet 8.0-13.0 mm
Temperature range from/to -40 °C / 85 °C
Mechanical operation > 100 Mating cycles
Additional information UL 2237 in preparation
with PE connection
Weight (g) 55.83
Customs tariff number 85369010
Country of Origin DE
Rated voltage 630 V
Rated impulse voltage 6000 V
Rated impulse voltage UL 6000 V
Rated current 12.0 A
Insulation resistance > 1010 Ω
Pollution degree 3
Overvoltage category III
Insulating material group I
EMC compliance unshielded
Housing material PA
Contact body material PA (UL94 V-0)
Contact material CuZn (brass)
Contact plating Au (gold)
REACH SVHC CAS 7439-92-1 (Lead)
SCIP number 2e2cebc2-9798-4e45-83db-3f5ba1376ca9
ETIM 9.0 EC002635
General Disclaim Notice
  1. The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
  2. The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
  3. To protect against unintentional opening of the connector, the thread between the housing and the connector head must be secured with a suitable cyanoacrylate adhesive when used in circuits with voltages dangerous to the touch. This does not apply to connectors used in SELV and PELV circuits according to IEC 61140 (EN 61140, VDE 0140-1).
  4. Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
  5. The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
  6. Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
  7. The plug connector is not suitable for mains voltages Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".
  8. To lock the cable connector with the device connector, the threaded ring is tightened "hand-tight" (approx. 60 cNm).
  9. In the case of cable connectors with a metal threaded ring, it is imperative to ensure a connection with the PE protective contact of the appliance connector. Connecting cables between appliance connectors that are not connected to the PE contact are not permitted. The user must ensure a continuous connection of the protective earth conductor.
M12-K