This male angled connector with screw locking and a pin count of 4 is according to its protection class IP67 Dust-tight and has complete protection against contact and protection against temporary immersion. It can be used in areas with a pollution degree of 3. In places where contamination can occur that is conductive or can become conductive through condensation. With temperatures ranges of -40 °C/85 °C is this unshielded M12-T coded male angled panel mount connector designed for both severe cold and severe heat and has the UL, VDE approval. Due to the qualified rated voltage of 63 V and the rated current of 12,0 A it is perfectly tuned for its field of application. It complies with the type standard DIN EN IEC 61076-2-111:2018-10 and VDE 0687-76-2-111:2018-10.
General features
Moreless
Part no. 99 0629 58 04
Connector design Male angled connector
Type standard DIN EN IEC 61076-2-111:2018-10;VDE 0687-76-2-111:2018-10
Version Connector pin angled
Connector locking system screw
Termination screw clamp
Degree of protection IP67
Cross-sectional area max. 1.50 mm² / AWG 16
Cable outlet 8.0-10.0 mm
Twistability 90° (4 coding options)
Temperature range from/to -40 °C / 85 °C
Mechanical operation > 100 Mating cycles
Weight (g) 27.50
Customs tariff number 85369010
Country of Origin DE
Rated voltage 63 V
Rated impulse voltage 1500 V
Rated current 12.0 A
Pollution degree 3
Overvoltage category III
Insulating material group II
EMC compliance unshielded
Housing material PA
Contact body material PA
Contact material CuZn (brass)
Contact plating Au (gold)
REACH SVHC CAS 7439-92-1 (Lead)
SCIP number 1a0259e2-4576-42bd-9531-f3fd4cb5fef8
eCl@ss 11.1 27-44-01-02
ETIM 9.0 EC002635
General Disclaim Notice
  1. The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
  2. Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
  3. To lock the cable connector with the device connector, the threaded ring is tightened "hand-tight" (approx. 60 cNm).
Downloads
Data sheet
Data sheet 99 0629 58 04
PDF
Data sheet, Data sheet 99 0629 58 04
Certificates
UL certificate
PDF, 1.05 MB
Certificates, UL certificate
Certificates
VDE certificate
PDF, 659.52 KB
REACH
99 0629 58 04
PDF
RoHS
99 0629 58 04
PDF
China RoHS
99 0629 58 04
PDF
CAD files
Select required format
M12-T
99 0629 58 04