Part no.: 79 3415 55 06
Snap-In Male cable connector, unshielded, moulded on the cable, 5 m
M8, series 718, Automation Technology - Sensors and Actuators
This male cable connector with snap-in locking system and a pin count of 6 is according to its protection class IP65 Dustproof and complete protection against contact. Protected against dust in harmful quantity. Protection against water jets (nozzle) from any angle.. It can be used in areas with a pollution degree of 3. In places where contamination can occur that is conductive or can become conductive through condensation. With temperatures ranges of -25 °C/70 °C is this unshielded M8 male cable connector designed for both severe cold and severe heat. Due to the qualified rated voltage of 30 V and the rated current of 1,5 A it is perfectly tuned for its field of application. It complies with the type standard DIN EN 61076-2-104.
General features
MorelessPart no. | 79 3415 55 06 |
Connector design | Male cable connector |
Type standard | DIN EN 61076-2-104 |
Cable length | 5 m (Standard 2 m and 5 m. Other lengths are available on request.) |
Version | Connector pin straight |
Termination | moulded on the cable |
Cross-sectional area | AWG 24 |
Weight (g) | 0.00 |
Customs tariff number | 85444290 |
Country of Origin | DE |
Electrical parameters
MorelessRated voltage | 30 V |
Rated impulse voltage | 800 V |
Rated current | 1.5 A |
Insulating material group | II |
EMC compliance | unshielded |
Material
MorelessREACH SVHC |
CAS 7439-92-1 (Lead) |
SCIP number | f1b8fc60-01fd-4d34-afaf-555c922af77e |
Classifications
MorelessETIM 9.0 | EC002638 |
Cable data
MorelessStructure of the cable | |
Single-lead insulation | PP |
Electrical properties | |
Conductor resistance | 79 Ω/Km (20°C) |
Mechanical properties | |
Bending cycles | > 2 million |
Other features | |
Halogen free | yes |
General Disclaim Notice
- The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
- The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
- To protect against unintentional opening of the connector, the thread between the housing and the connector head must be secured with a suitable cyanoacrylate adhesive when used in circuits with voltages dangerous to the touch. This does not apply to connectors used in SELV and PELV circuits according to IEC 61140 (EN 61140, VDE 0140-1).
- Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
- The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
- Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
- Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".
- To lock the cable connector with the device connector, the threaded ring is tightened "hand-tight" (approx. 40 cNm).
Downloads